
Technical
Notes 39 - Testing for Engineered Brick Masonry- Brick and Mortar
November 2001![]()
Abstract: Testing of brick, mortar and grout is often required prior to and
during construction of engineered brick masonry projects. The tests involve a combination of
laboratory and field procedures which are described in various ASTM
standards. The extent of testing is a
decision made by the engineering or architectural firm responsible for the
masonry design, and may consist of only a few laboratory tests to determine the
properties of the brick units, or may involve extensive laboratory and field
sampling and testing. This Technical Notes describes the testing of
materials; other issues in this series describe testing of brick masonry
assemblages.
Key Words: brick, engineered
brick masonry, grout, mortar, quality
control, testing.
INTRODUCTION
The use of engineered brick
masonry in the construction of loadbearing structures requires that the
standard methods for determining the physical properties of both the materials
and the masonry assemblages be strictly followed. The standards and specifications for engineered brick masonry are
based, for the most part, on the results of American Society for Testing and
Materials (ASTM) methods of testing.
It is not the intent of this Technical Notes to supersede the various
applicable ASTM standards, but to supplement them. The ASTM standards have been carefully developed by balanced
technical committees composed of people experienced and knowledgeable in their
chosen fields. Therefore, if the
prescribed methods of tests are not adhered to, inaccurate and inconsistent
test data and erroneous conclusions can result. This can be quite serious when the design of a masonry bearing
wall structure is based on such tests, or when such tests are used as quality
controls during construction.
This Technical Notes covers testing of masonry materials for obtaining
information needed to determine design properties for engineered brick
masonry. Additional testing required
for assessment of material compliance to various ASTM specifications is not
included. In addition, field testing of
brick, mortar and grout for quality control is discussed.
This Technical Notes is the first in a series on testing. Other Technical
Notes in this series discuss the construction, preparation and testing of
masonry assemblages (in the laboratory); and the sampling, preparation and
handling of jobsite test specimens for the purpose of quality control of the
construction.
ENGINEERED BRICK MASONRY STANDARDS
There are several standards
used in the United States for the design of brick masonry structures, all of
which contain some requirements for testing of masonry materials or
assemblages. Likewise, other standards
and building codes require testing in order to establish various design
parameters.
In addition to predesign and
preconstruction testing, testing for the purpose of quality control is often
implemented. Building Code Requirements for Masonry Structures (ACI 530 / ASCE 5
/ TMS 402-99) and Specification for
Masonry Structures (ACI 530.1/ ASCE 6 / TMS 602-99) [3], known as the MSJC
Code and Specifications, contain several quality assurance requirements. For example, the MSJC Code and Specification
require that the initial rate of absorption (IRA) of brick at the time of
laying not exceed 1 gram per sq in. per min. ASTM C 62, ASTM C 216 and ASTM C
652 also recommend that the limit on IRA be 30 g/30 in.2/min. The determination of this property may be
made in the laboratory on oven-dry brick, or at the construction site as a
field test. The tests outlined within
this Technical Notes are those which
are most commonly performed to satisfy the requirements of the MSJC Code and
Specification.
TESTING STANDARDS
The ASTM standards which are
most frequently utilized when testing brick masonry materials should be readily
available to all laboratory personnel, and to individuals involved in field
testing. The applicable standards are
as follows:
Clay Masonry Units -ASTM C 67, Standard Test Methods of
Sampling and Testing Brick and Structural Clay Tile
Mortar -ASTM C 270, Standard
Specification for Mortar for Unit Masonry
-ASTM C 91,
Standard Specification for Masonry Cement
-ASTM C 109,
Standard Test Method for Compressive Strength of Hydraulic Cement Mortars
(Using 2-in. or 50-mm Cube Specimens)
-ASTM C 780,
Standard Test Method for Preconstruction and
Construction Evaluation of Mortars for Plain and Reinforced Unit Masonry
Grout -ASTM C 476, Standard
Specification for Grout for Masonry
-ASTM C 1019,
Standard Test Method for Sampling and Testing Grout
For the most part, these
standards provide clear and concise explanations of the procedures for sampling
and testing masonry materials; however, for the novice, some areas may present
some confusion. The following sections will explain some of the procedures
required by the various ASTM standards.
BRICK TESTING FOR ENGINEERED BRICK MASONRY
The strength of brick varies
considerably, depending on raw material, method of manufacture and degree of
firing. The range in compressive
strength is on the order of 2000 psi to in excess of 20,000 psi. The MSJC Code does not dictate minimum
compressive strength requirements for brick, but since the allowable stresses
and elastic moduli of masonry are a function of compressive strength of brick,
testing to determine compressive strength is required.
For the determination of unit
compressive strength, f'b, the procedures given in ASTM C 67 [1] should be
followed.
The initial rate of absorption
(IRA) is another important property. If
the IRA of brick exceeds an acceptable upper limit, problems with excessive
shrinkage of mortar and grout, and poor bond, are apt to occur. The procedures for determining the IRA, in
the laboratory and in the field, are contained in ASTM C 67.
Compressive Strength
Specimen Size. ASTM C 67 requires that the specimen be full height and width,
and approximately one-half of a brick in length, plus or minus 1 in. (25
mm). For example, an 8-in. (200 mm) long
brick may be tested using a piece of brick with a length between 3 and 5 in.
(75 and 125 mm). However, if the
testing machine being used is not capable of providing sufficient force to
crush the approximate half-brick, a piece of brick having a length of
one-quarter of the original full brick length may be used, so long as the total
cross-sectional area is not less than 14 in.2 (90 cm2),
see Figure 1.

Compressive Strength Specimens
FIG. 1
Although ASTM C 67 does not
specifically state the method in which the samples are to be obtained, it has
been common practice to use pieces of brick which are left over from modulus of
rupture tests. If modulus of rupture
tests are not being performed, then sawing the units to the desired size is
acceptable. A minimum of five specimens
is required.
The compressive strength test
specimens should be oven-dried. The
amount of moisture in the brick can affect its compressive strength - the
higher the moisture content, the lower the apparent strength. Therefore, by drying the specimens before
testing, one variable that can affect the results is eliminated. If they are wet-cut with a masonry saw, the
drying should follow the cutting. If a
wet capping material, such as high-strength gypsum, is used, it is generally
agreed that the small amount of moisture absorbed by the specimens will not
make additional oven drying necessary.
The 24-hr curing period in laboratory air will suffice.
Capping Specimens. The importance of careful capping procedures cannot be
over-emphasized. Brick units, by their
inherent nature, are not perfectly formed and their bearing surfaces may not be
parallel and free from surface irregularities.
The purpose of capping the bearing surfaces is to assure reasonably
parallel and smooth opposite bearing surfaces; thus reducing the likelihood of
uneven bearing and stress concentrations, and the resulting premature failure
of the test specimen.
Laboratory technicians
responsible for capping compressive test specimens should be thoroughly
familiar with the capping procedures prescribed in ASTM C 67. Poor caps, resulting from careless capping
techniques, can result in erratic test results and a lowering of the apparent
compressive strengths of the specimens.
Placing Specimens
in Testing Machine. The requirement in ASTM C 67
that the specimen be centered under the spherical upper bearing block within
1/16 in. (1.6 mm) is not a capricious one.
The introduction of an eccentric load, if the specimen is not carefully
centered, can result in a lower apparent compressive strength for the test
specimen. It should be understood,
however, that this requirement assumes that the specimen is symmetrical about
both horizontal axes or its center of gravity.
For symmetrical specimens, the center of gravity will be the geometrical
center of the unit. Such is not the
case with unsymmetrical test specimens.
Therefore, the centers of gravity of unsymmetrical specimens should be
determined and marked, and it is those marks that should be aligned with the
center of the upper bearing block.
To determine the center of
gravity for an unsymmetrical test specimen, a small steel rod, 1/8 in. to 1/4
in. (3 to 8 mm) in diameter, may be used.
The location of the center of gravity is determined by finding the
balance point of the brick specimen. To place the specimen over the rod in the
exact position such that it balances perfectly is difficult, but a very good
estimate of this location is not hard to achieve.
Speed of Testing. The speed of testing specified in ASTM C 67 should be adhered to,
primarily for the purpose of obtaining consistent results. Past experience on the effect of the rate of
loading on the compressive strength of specimens has shown that, as the rate
increases, there can be significant increases in the apparent compressive
strengths of the specimens. The
requirements of ASTM C 67, while not particularly specific, do provide a
moderate rate of loading which, if followed, will produce consistent results
that will represent more accurately the true compressive strengths of the
specimens.
ASTM C 67 specifies that the
specimen should be loaded to one-half of the expected maximum load, and then
the rate should be adjusted such that the test is completed in not less than
one minute and not more than two minutes.
For this reason, it is a good idea to do one or two preliminary tests to
get an estimate of the maximum strength.
Figure 2 illustrates the time vs. loading criteria of ASTM C 67.

Compressive Test Loading Rate
FIG. 2
Determination of
Minimum Net Area (Percent Voids). There are two
reasons for determining the void area of brick: the first reason is to obtain
the percentage of voids (percentage coring) in order to assess whether the
brick will be classified as solid or hollow brick; the second reason is to
obtain the average net cross-sectional area for determination of net area
compressive strength of the units. ASTM C 216 and C 62 for solid brick, and
ASTM C 652 for hollow brick require calculation of gross area compressive strength.
If the net area compressive
strength is required, the section "Measurement of Void Area in Cored
Units" in ASTM C 67 should be followed.
To perform these measurements, a sample of ten brick is specified by
ASTM C 67. Following the procedure in
this section, the cores are filled with sand.
The sand is then placed in a graduated cylinder to determine the
volume. Using the equation given in
ASTM C 67 for percent void area, the void area can be determined. The net area can be determined by
subtracting the void area from the gross area.
Calculation and
Report. The compressive strength is determined by
dividing the maximum compressive load by the gross cross-sectional area of the
specimen. If the net area compressive
strength is required, the net area, as determined in the previous section, must
be used to obtain the desired results.
Since five specimens are used, the arithmetic average should be
determined.
Initial Rate of Absorption
The initial rate of absorption
(IRA) is an important property of brick because it affects mortar and grout
bond. Brick IRA and mortar retentivity
should be considered when selecting brick and mortar type. If the initial rate of absorption is over 1
gram per minute per in2, brick will absorb moisture from the mortar
or grout at a rapid rate, and may impair the strength and extent of the bond. Thus, determining the IRA is important.
In the laboratory, the IRA is
measured using brick which are oven-dried to equilibrium. The IRA of a dry brick is apt to be higher
than one which contains some moisture.
The field test for initial rate of absorption is performed on brick in
their field condition, i.e., no attempt is made to dry the units. The laboratory test will give an idea of the
order of magnitude of the IRA and the field test can be used to determine if
additional wetting is necessary.
Laboratory
Procedure. As previously mentioned, the laboratory
procedure is performed on oven-dried specimens. Five full-size specimens are required. The technician performing the test should be aware that the
larger the tray size, the less effect the absorption has on the water
level. ASTM C 67 requires a tray with a
cross-sectional area of at least 300 in.2 (1935.5 cm2). For a brick with an IRA of 40 g/min/30 in.2,
the water level would drop less than 1/100 in., which is hardly
measurable. Nevertheless, ASTM C 67
provides recommendations on maintaining the water level. Figure 3 illustrates the tray with a brick
positioned for testing. The method is
relatively straightforward and easy to perform. The results are reported in grams of water gained per 30 sq in.
when the brick are immersed in 1/8 in. (3 mm) of water for 1 min. The calculation of IRA is as follows:
IRA = 30 W / LB (Eq. 5)
where: W = actual gain in weight of specimen in
grams,
L = length of
specimen, in in. and
B = width of
specimen, in in.
What some laboratory
technicians fail to realize, however, is that the above equation is for
specimens that are not cored. If the test specimens are cored brick, or are non-prismatic, the net area must be substituted for LB in
Eq. 5.

Determination of IRA
FIG. 3
Field Procedures. Brick units on the jobsite may have a different rate of
absorption than that of the same units tested for IRA in the laboratory. The IRA may be lower due to moisture which brick
absorb after leaving the manufacturing plant.
Two tests are available for field determination of brick
absorption. One is an ASTM procedure,
described in ASTM C 67, which measures quantitatively the absorption rate. The other is an approximate, but effective,
test which is not covered by an ASTM standard, and yields a qualitative
indication of the bricks' absorption rate and necessity for wetting prior to
use.
ASTM Field Method for IRA - This method is described in
detail in ASTM C 67, and is accomplished through volumetric means rather than
by weight measurements. Using this
method, the brick are placed in a pan of water for 1 min. removed and the
quantity of water remaining in the pan is measured using a pycnometer (Fig.
4). The pycnometer is used to measure
the initial quantity of water to be placed in the pan. The difference in the original amount of
water and the quantity remaining after placement of the brick into the pan for
1 min is the amount absorbed by the brick.
It is very important to use the correct size pan and to wet and drain
the pan prior to testing.

Pycnometer
FIG. 4
Test for Wetting Brick - The following test is useful
for determining the necessity of wetting brick prior to use:
A circle, approximately 1 in.
(25 mm) in diameter, is drawn on the bed surface of the brick, using a wax pencil
and a twenty-five-cent coin as a guide.
Twenty drops of water are placed into the circle using an
eyedropper. If, after 90 seconds, all
of the water has been absorbed, wetting the brick prior to placement is
recommended.
MORTAR TESTING FOR ENGINEERED BRICK MASONRY
Technical Notes 8 Series discusses the various
types of mortar, properties and mix designs.
Also, ASTM C 270, Specification for Mortar for Unit Masonry, gives both
prescriptive and performance requirements for mortar. Another standard specification for mortar, BIA M1-88, provides
recommendations on selection proportions and test requirements of portland
cement-lime mortars. This section will
outline the various mortar tests which are important when designing and
building engineered brick masonry elements.
Laboratory Testing of Mortar
Laboratory testing of mortar is
performed in accordance with ASTM C 270 [2]and other standards referenced in
ASTM C 270. The tests are performed on mortar samples which are prepared in the
laboratory. ASTM C 270 is not a specification to determine mortar
strength and properties through field testing.
The amount of testing required by ASTM C 270 depends on the method in
which the mortar is specified, i.e., proportion or property specification. If the mortar is specified by the proportion
specifications, there are no testing
requirements for mortar. For mortars
specified by the property specifications, water retention, compressive strength
and air content tests must be performed.
The following sections describe
the methods of tests for mortar which are specified by the property specifications.
Water Retention. ASTM C 270 refers to the procedures of ASTM C 91 for water
retention determination, except that the laboratory-mixed mortar shall be of
the same materials and proportions to be used in the construction. Since the water content of mortar used on
the jobsite varies somewhat, and is not a specified quantity, the laboratory
technician should proportion the cementitious materials and sand in accordance
with the job specification and add sufficient water to bring the flow up to 110
+/- 5%.
To perform the water retention
tests, the technician should review ASTM C 91 on Water Retention, ASTM C 305 on
Mechanical Mixing, and ASTM C 109 on Performing Flow Tests. The flow test apparatus must meet the
specifications of ASTM C 230. The chart
in Fig. 5 indicates the ASTM standards relative to water retention testing of
mortar specified by the property
specifications.

Related ASTM Standards for Property Specifications
FIG. 5
Compressive
Strength. Compressive strength testing of
laboratory-prepared mortar is required under the ASTM C 270 property
specifications. To determine
compressive strength, samples are to have the same proportions as in the actual
construction. As with the water
retention test, the amount of water to be used is not clearly stated;
therefore, it is recommended that sufficient water be used to bring the flow to
110 +/- 5%. As shown in Fig. 5, other
associated ASTM standards which must be used are ASTM C 109, C 305 and C 230.
The technician should become
familiar with the procedures of ASTM C 109 for specimen molding and load
application since these procedures must be followed closely in order to obtain
reliable results.
Air Content. Air content determination is the third and last property which
must be assessed for mortars specified under the property specifications. The air content is determined using a
weight-volume relationship to determine the absolute volume of solids and
water. ASTM C 91 and ASTM C 185 are
used to determine air content, except that the equation for percent air content
is given in ASTM C 270. The equation for air-free mortar density is:
(Eq. 2)
and the volume of air in percent is
(Eq.
3)
where: W1 = weight
of portland cement, g,
W2 =
weight of hydrated lime, g,
W3 = weight
of masonry cement (if used), g,
W4 = weight
of sand, g,
Vw = volume
of water used, mL,
P1 = unit
weight of air-free portland cement, g/cm3,
P2 = unit
weight of air-free hydrated lime, g/cm3,
P3 = unit
weight of air-free masonry cement (if used), g/cm3,
P4 = unit
weight of air-free sand, g/cm3,
Wm = weight
of 400 mL of mortar, g.
The air-free unit weights of
the various materials in Eq. 2 are equal to the specific gravity of the
material times the unit weight of water (which is unity); thus, the unit weight
is numerically equal to the specific gravity.
The specific gravity for the various materials should be obtained from
the manufacturers or determined by testing.
Table 1 gives the approximate specific gravities for several mortar
materials

In performing the air-content
tests, it is very important to weigh and measure the quantities accurately,
since errors in weights and volumes would have significant impact upon the
calculated air content.
Field Testing of Mortar
For purposes of quality
control, field testing of mortar is sometimes required. Field testing should not be confused with
laboratory testing, or be performed using the standards and procedures for
laboratory testing of mortar. The
appropriate standard for this type of testing is ASTM C 780 "Standard Test
Method for Preconstruction and Construction Evaluation of Mortars for Plain and
Reinforced Unit Masonry". The main
purposes of field testing is to ensure that mortar is proportioned properly by
the mixer operator, and to obtain an indication of variability or change in
constituent materials, quality and performance.
There are several tests which
are covered in ASTM C 780, not all of which are required. Eight tests are outlined in the Annexes of
ASTM C 780 which are: A1) Consistency by Cone Penetration Test Method, A2)
Consistency Retention of Mortars for Unit Masonry, A3) Initial Consistency and
Consistency Retention or Board Life of Masonry Mortars Using a Modified
Concrete Penetrometer, A4) Mortar Aggregate Ratio Test Method, A5) Water
Content Test Method, A6) Mortar Air Content Test Method, A7) Compressive
Strength of Molded Masonry Mortar Cylinders and Cubes and A8) Splitting Tensile
Strength of Molded Masonry Mortar Cylinders.
The testing agency and the
specifier should be aware that the compressive strength of mortar, as
determined by field testing, does not have
to meet the minimum compressive strength requirements of ASTM C 270.
The specifier must decide which
of the eight tests is to be performed, then preconstruction testing of the
materials can be performed in order to establish requirements for construction
site-sampled mortar.
A complete discussion of the
test procedures of ASTM C 780 is not within the scope of this Technical Notes; therefore, the
technician in charge of performing the tests should become thoroughly
knowledgeable with ASTM C 780 and its referenced documents.
GROUT TESTING FOR ENGINEERED BRICK MASONRY
The specification for grout for
engineered brick masonry, ASTM C 476, does not require any laboratory
testing. Experience with grout mixed in
accordance with the provisions of ASTM C 476 has been extremely favorable, and
grout, therefore, does not require extensive testing if mixed with the materials
and in the proportions stipulated by the standard.
There is a relatively new
standard for both field and laboratory sampling and compressive testing of
grout used in masonry construction, entitled ASTM C 1019, "Standard Test
Method for Sampling and Testing Grout".
Sampling and Testing Grout for Engineered Brick Masonry
According to ASTM C 1019, the
use of the standard may be to select grout proportions by comparing test values
or as a quality control test for uniformity of grout preparation during construction. The standard specification for grout, ASTM C
476, does not contain provisions for mixing grout to property specifications;
therefore, the use of ASTM C 1019, at this time, for grout mix design is not advised. For purposes of quality assurance, the grout
testing standard may be useful.
The specimens are prepared by
using masonry units as forms (Fig. 6).
The masonry units are those which are to be used in the project under
construction or to be constructed. The
laboratory technician may find it strange to use the brick units as forms, but
the reason is to simulate the conditions of the grout after placement into the
brick masonry element. Grout is placed
with a high water/cement ratio, slump of 10 to 11 in. (250 mm to 275 mm), in
order to facilitate consolidation and eliminate voids. Due to the absorptive nature of the masonry,
the water content of the grout is reduced after placement.
The methods of sampling and
testing, as described in ASTM C 1019, are easily accomplished; therefore,
additional description and explanation will not be given in this Technical Notes.

Grout Mold Using 2 ¼ in. (152.4 mm)
High Standard Size Brick
FIG. 6
SUMMARY
This Technical Notes has discussed testing of brick, mortar and grout
used in engineered brick masonry. Most
laboratory and field tests are covered by ASTM standards. Testing agencies using these tests should be
fully aware of the procedures and limitations, so that improper application and
erroneous results are avoided.
The information and suggestions
contained in this Technical Notes are
based on the available data and the experience of the engineering staff of the
Brick Industry Association. The
information contained herein must be used in conjunction with good technical
judgment and a basic understanding of the properties of brick masonry. Final decisions on the use of the
information contained in this Technical
Notes are not within the purview of the Brick Industry Association and must
rest with the project architect, engineer and owner.